58. PROPORTIONAL + DEADBAND FULL HEAT SET

Write Command: 41

Read Command: 76

Interpret: To send the low set temperature, multiply the decimal value by 100

10

and convert to hexadecimal. To

read the low set temperature, convert the returned hexadecimal value to decimal, and then divide by

100

10

.

If the INPUT1 sensor reaches this temperature, the controller will provide maximum heating output

power.

59. PROPORTIONAL + DEADBAND START HEAT SET

Write Command: 42

Read Command: 77

Interpret: To send the low dead set temperature, multiply the decimal value by 100

10

and convert to

hexadecimal. To read the low dead set temperature, convert the returned hexadecimal value to

decimal, and then divide by 100

10

.

If the INPUT1 sensor is greater than the PROPORTIONAL + DEADBAND START HEAT SET temperature

but less than the PROPORTIONAL + DEADBAND START COOL SET temperature, then the controller will

not provide any output power for cooling or heating. If the INPUT1 sensor is less than the

PROPORTIONAL + DEADBAND START HEAT SET temperature, the controller will proportionally increase

the amount of heating output power.

60. PROPORTIONAL + DEADBAND START COOL SET

Write Command: 43

Read Command: 78

Interpret: To send the high dead set temperature, multiply the decimal value by 100

10

and convert to

hexadecimal. To read the high dead set temperature, convert the returned hexadecimal value to

decimal, and then divide by 100

10

.

If the INPUT1 sensor is greater than the PROPORTIONAL + DEADBAND START HEAT SET temperature

but less than the PROPORTIONAL + DEADBAND START COOL SET temperature, then the controller will

not provide any output power for cooling or heating. If the INPUT1 sensor is greater than the

PROPORTIONAL + DEADBAND START COOL SET temperature, the controller will proportionally

increase the amount of cooling output power.

61. PROPORTIONAL + DEADBAND FULL COOL SET

Write Command: 44

Read Command: 79

Interpret: To send the high set temperature, multiply the decimal value by 100

10

and convert to hexadecimal. To

read the high set temperature, convert the returned hexadecimal value to decimal, and then divide by

100

10

.

If the INPUT1 sensor reaches this temperature, the controller will provide maximum cooling output

power.