User Defined Lookup Table

This table, stored in EEPROM, is used to define a profile of the temperature of the sensor versus a reference

voltage. The table consists of 129 integer pointers, ranging from 0 to 128. Pointer 0 corresponds to 0 volts; Pointer

128 corresponds to 5 V. The controller will linearly interpolate values between the indexed values with the

remaining bits. This is a 16 bit signed number.

62. USER DEFINED LOOKUP TABLE POINTER

Write Command: 90

Read Command: NA

Interpret: Range 0 to 128

10

; sets the index pointer for writing or reading a value.

63. USER DEFINED LOOKUP TABLE VALUE WRITING

Write Command: 91

Read Command: NA

Interpret: The USER DEFINED LOOKUP TABLE POINTER must be set first before using this command. The value

for this location ranges from -32767

10

to 32768

10

. This corresponds to a range -327.67 °C to

+327.68 °C.

64. USER DEFINED LOOKUP TABLE VALUE READING

Write Command: NA

Read Command: 92

Interpret: Send the index value with the Read Command to receive back the indexed value.

Example: Send 0 with the 92 command to see the value at TABLE[0].

65. OUTPUT CURRENT COUNTS

Write Command: NA

Read Command: 07

Interpret: Output current reading in A/D counts; approximately 15

10

counts/amp.

66. OUTPUT CURRENT A/D COUNTS OVERCURRENT DETECT VALUE

Write Command: 45

Read Command: 7a

Interpret: Overcurrent compare value of above current counts (greater than or equal trips over current alarm).

67. OUTPUT OVER CURRENT RETRIES BEFORE SHUTDOWN

Write Command: 46

Read Command: 7b

Interpret: Amount of output retries during overcurrent condition allowed before output shutdown. 30000

10

value is constant retry.

68. SPARE (non-volatile) EEPROM MEMORY

Write Command: 80

Read Command: 81

Interpret: When writing, first use the USER DEFINED LOOKUP TABLE POINTER command to set the index.

Read value by sending index with read command request.

Valid index values are 0 through 9 (10 total locations). Valid values are 0 to 255

10

.