magnitude of the voltage to the thermoelectric device is controlled by the analog output signal and a

programmable linear-output power supply. Temperature control is achieved in the following manner:

a) The analog output signal on JP2-5 is used to send a 0 to 10 Vdc analog control signal to an external

linear power supply. This 0-10Vdc signal corresponds to 0 to 100% output power, and is independent

of the required output polarity (it is magnitude only). See also the options in the OUTPUT BOX for

additional details where the maximum output signal can be reduced to match the requirements of

the power supply you intend to use.

NOTE: The analog output is always present, regardless on if the controller is in ANALOG OUT mode or

not.

b) The linear-output programmable power supply uses this 0-10V control signal to adjust its output from

0 V to its full-scale voltage. This creates a high-power, variable analog voltage for the

thermoelectrics.

c) The voltage generated by the linear-output power supply is fed back into controller at JP7-3 and

JP7-4.

d) The polarity of this voltage is then kept positive or reversed depending on if heating or cooling is

needed (H-Bridge output is +100% or -100%)

e) The voltage is sent to the thermoelectric device at terminals JP7-1 and JP7-2. Thus, full linear control

with both magnitude and polarity is accomplished.

2. RAMP/SOAK—the controller will follow a sequence of set points defined by the ramp/soak profile. See Ramp/Soak

Configuration below for further details.

3. PROPORTIONAL+DEAD BAND—the controller will provide linear power output between two temperatures in both

heating and cooling mode. A dead band is allowed between these heating and cooling points where no power is

sent to the thermoelectric devices. This is useful with outdoor enclosures that have a broad operating

temperature range and only need cooling or heating at times of extreme temperatures. Otherwise, when the

enclosure temperature is within the pre-defined temperature range, output power can be off in order to save

energy. See PROPORTIONAL+DEAD BAND CONFIGURATION below for further details.