22. ALARM LATCH FUNCTION

Write Command: 2b

Read Command: 5f

Interpret:

0 == NO LATCHES

1 == ALARM1 LATCH

2 == ALARM 2 LATCH

3 == ALARM 1&2 LATCH

23. ALARM1 DEADBAND

Write Command: 2d

Read Command: 61

Interpret: The span in temperature that the control sensor (INPUT1) must move before the ALARM1 output is

toggled off. For writing, multiply the desired deadband by 100

10

, and then convert to hexadecimal. For

reading, convert the hexadecimal value to decimal, and then divide by 100

10

.

1.00

10

degree would be 100

10

.

20.00

10

degree would be 2000

10

.

24. ALARM2 DEADBAND

Write Command: 2e

Read Command: 62

Interpret: The span in temperature that the secondary sensor (INPUT2) must move before the ALARM2 output is

toggled off. For writing, multiply the desired deadband by 100

10

, and then convert to hexadecimal. For

reading, convert the hexadecimal value to decimal, and then divide by 100

10

.

1.00

10

degree would be 100

10

.

20.00

10

degree would be 2000

10

.

25. SENSOR FOR ALARM2

Write Command: 3a

Read Command: 6e

Interpret:

0 == monitors INPUT2 for ALARM2

1 == monitors INPUT1 for ALARM2

26. ANALOG OUTPUT MULTIPLIER

Write Command: 2f

Read Command: 63

Interpret: For writing, multiply the desired analog output multiplier by 100

10

, and then convert to hexadecimal.

For reading, convert the hexadecimal value to decimal, and then divide by 100

10

. The allowable range

is 0 to 1.00.

0.00 multiplier would be 0

0.50 multiplier would be 50

10

1.00 multiplier would be 100

10

27. LATCH CLEAR

Write Command: 75

Read Command: NA

Interpret: Send this command to reset alarm latches.

28. OUTPUT ENABLE

Write Command: 30

Read Command: 64

Interpret:

0 == OFF

1 == ON

80