PROPORTIONAL + DEADBAND MODE CONFIGURATION

This feature is typically used with air-to-air cooling assemblies (TE Technology AC-XXX models) when controlling the internal

temperature of an enclosure. This feature is particularly useful to minimize power usage for applications that have a

relatively wide portion of their operating temperature range in which heating or cooling is not required. The controller

would only apply power if the sensor temperature were at the extremes of the operating temperature range.

Clicking on the “CONFIGURE PROPORTIONAL+DEADBAND MODE” OK button calls up the following screen:

The controller can be configured so that power is applied proportionally based on four different temperatures. The

controller provides no power output when the sensor temperature is between the two temperatures defined by START

HEAT and START COOL. If the sensor temperature were to drop below the START HEAT temperature, the controller would

then begin proportionally increasing power in the heating mode such that 100% would be applied if the sensor temperature

were to decrease to (or go below) the FULL HEAT temperature. Likewise, if the sensor temperature were instead to start

increasing past the START COOL temperature, then the controller would begin proportionally increasing power in the

cooling mode from such that -100% would then be applied if the sensor temperature were to increase to (or exceed) the

FULL COOL temperature.

In order for this feature to work properly, be sure that the FULL HEAT temperature is less than the START

HEAT temperature. Similarly, be sure that the FULL COOL temperature is greater than the START COOL

temperature.