4 diagnostic messages – Honeywell SMV 3000 User Manual

Page 140

Advertising
background image

128

SMV 3000 Transmitter User’s Manual

1/99

11.4

Diagnostic Messages,

Continued

Diagnostic Messages,
continued

Table 32

Non-Critical Status Diagnostic Message Table, continued

SMV Status

SCT Status Message SFC Display Message TDC Status Message

Possible Cause

What to Do

2-1

Excess Zero Correct

PV1

Or

Zero Correction is Out of

Limits

STATUS TAG ID.#

EX. ZERO COR PV1

EX. ZERO COR PV1

ZERO correction factor is outside
acceptable limits for PV1 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.

Verify calibration.

If error persists, call the
Solutions Support Center

4-1

Excess Zero Correct

PV2

STATUS TAG ID.#

EX. ZERO COR PV2

EX. ZERO COR PV2

ZERO correction factor is outside
acceptable limits for PV2 range.
Could be that transmitter was in
input or output mode during a
CORRECT procedure.

Verify calibration.

If error persists, call the
Solutions Support Center

8-1

Excess Zero Correct

PV3

STATUS TAG ID.#

EX. ZERO COR PV3

EX. ZERO COR PV3

ZERO correction factor is outside
acceptable limits for PV3 range.

Verify calibration.

If error persists, call the
Solutions Support Center

9-1

Excess Zero Correct

PV4

STATUS TAG ID.#

EX. ZERO COR PV4

EX. ZERO COR PV4

ZERO correction factor is outside
acceptable limits for PV4 range.

Verify calibration.

If error persists, call the
Solutions Support Center

9-5

In Cutoff PV4

STATUS TAG ID.#

IN CUTOFF PV4

IN CUTOFF PV4

Calculated flow rate is within
configured low and high limits for
PV4 low flow cutoff.

Nothing – wait for flow rate to
exceed configured high limit.

Verify that flow rate is in cutoff.

5-4

Input Mode PV1 (DP)

STATUS TAG ID.#

INPUT MODE PV1

INPUT MODE PV1

Transmitter is simulating input for
PV1.

Exit Input mode:

SCT – Press “Clear Input Mode”

button on the DP InCal tab.

SFC – Press [

SHIFT

], [

INPUT

], and

[

CLR

] keys.