SMV 3000 Transmitter User’s Manual

1/99

162

A.5

Configuration,

Continued

ATTENTION

The actual engineering unit values available in a system will depend upon
the LCN software release. See Section 10 in the PM/APM Smartline
Transmitter Integration Manual for
release dependent EU details.

DE_CONF Parameter

While the DECONF selections are the same for all transmitters, the
corresponding SCT 3000 selections for PV Type may differ. Table A-6
compares the PV Type selections for SMV 3000 with PED DECONF
parameter selections for reference.

Table A-6

DECONF and PV Type Parameter Entry Comparison

IF PED DECONF entry is …

THEN comparable SCT 3000 PV Type
entry can be any one of the following …

PV

Not Applicable for SMV 3000.

PV_SV

Not Applicable for SMV 3000.

PV_DB

PV1,
PV1 and PV2,
PV1 - PV3, or
PV1 - PV4

PV_SV_DB

PV1 w/SV1,
PV1 and PV2 w/SV1
PV1 - PV3 w/SV1, or
PV1 - PV4 w/SV1

URL Parameter

Table A-7 lists example Upper Range Limits for a given SMV 3000
transmitter PV. Remember that you can enter the desired URL for the PV4
range through the SCT 3000, but URL for PV1, PV2, and PV3 is a read
only fixed value (determined by SMV model and process temperature
sensor type).

Table A-7

Example URLs for a SMV Transmitter Model SMA125.

IF Process Variable Number is…

THEN URL is …

PV1

400 inH2O

PV2

750 psia

PV3

850

°

C (varies per sensor type)

PV4

configurable

ATTENTION

If you leave the URL parameter blank, you can upload the transmitter
database through the detail display commands to resolve the resulting
database mismatch error. The URL is always part of the transmitter’s
database.

Continued on next page