Honeywell SMV 3000 User Manual

Page 176

Advertising
background image

SMV 3000 Transmitter User’s Manual

1/99

164

A.6

Operation Notes

Generic Operations

Most operator actions initiated through Detail displays at the Universal
Station are generic for all Smartline transmitters. Refer to Section 7 in the
PM/APM Smartline Transmitter Integration Manual for details about
these generic operations.

This section outlines some differences in operations that are unique to the
multivariable STIMV IOP and the SMV 3000 transmitter in particular.

Detail Display
Difference

Page 2 of the Detail display for a multivariable STIM point includes an
additional field in the lower right hand corner for PV Number and Number
of PVs identification as shown in Figure A-6. This lets you quickly
identify what PV number you are viewing and how many PVs are
associated with this given SMV 3000 transmitter.

Figure A-6

Detail Display with PV Number and Number of PVs Field.

F101

SMV SLOT 1 - DIFF PRESS 03 UNIT 01

CONFIG PAGE

PVFORMAT 01
PVSRCOPT ALL
PVCLAMP

CLAMP

PVALDR ONE
PVALDEBEU 2.0000
INPTDIR REVERSE
LOCUTOFF -------

_________________ CONFIGURATION DATA ________________

PVCHAR LINEAR
SENSRTYP SPT_DP
PIUOTDCF OFF
BADPVPR LOW
PVHHPR NOACTION
PVHIPR NOACTION
PVLLPR NOACTION

PVLOPR NOACTION
PVROCPPR NOACTION
PVROCNPR NOACTION

______________ SMART TRANSMITTER DATA ______________

STITAG FT3011
SENSRTYP SPT_DP
PVCHAR LINEAR
CJTACT OFF
PIUOTDCF OFF
DECONF Pv_Sv_Db

PVRAW 50.000
URL 400.000
URV 250.000
LRV 0.00000
LUL 0.00000
STI_EU INH2O

SECVAR 21.5762
DAMPING 0.00000
SERIALNO 10775120
STISWVER 2.5
STATE OK
COMMAND NONE

TRANSMITTER SCRATCH PAD:
TRANSMITTER STATUS :

1 OF 1

23 Jun 98 11:15:23 6

PV Number

Number of PVs

Database Mismatch
Parameters

The following parameters are added to the list of parameters that the
STIMV IOP checks for database mismatches between itself and the
transmitter.

• PV Number

• Number of PVs

Continued on next page