Proper 240Vac 20A service requires the installation site be:

• Equipped with a 240Vac duplex receptacle to provide power to the power supply and peripheral

equipment.

• Have aNEMA 6-15R receptacle is protected by a single, 2-pole, common trip 15A circuit breaker

inside the service entrance.

• Checked to NEC CODE to verify proper wire AWG (suggested wire gauge is 14AWG).
• Equipped with a grounding clamp on the enclosure to facilitate dedicated grounding.

Utility Power Connection Notes, continued

LI (Black)

Neutral Bus

LI

L2

Grounding Point Made

to Enclosure Wall

Copper Ground Wire

#8 AWG (Minimum)

Breaker

L2 (Red)

To Utility

Neutral (White)

Typical 240Vac Service Entrance Wiring

When bonding the box to a neutral plate is required, use the long green bonding screw provided

(Alpha P/N 523-011-10, Square D P/N 40283-371-50).