48volt, 1350va – Alpha Technologies XM2, XM2-HV, XM2-HP User Manual

Page 19

Advertising
background image

1.2

Intelligent CableUPS Layout

, continued

1.2.2 Inverter Module Overview

The removable inverter module provides uninterrupted power to the ferroresonant

transformer (via the batteries) during line failures. During line operation, the inverter
charges the batteries using a three-stage (BULK, ACCEPT and FLOAT

) charger.

Each inverter module and transformer module is labeled to indicate its voltage and
current rating. The power supply also carries a voltage and current rating label. It
is very important the inverter module is installed only in a power supply with the
same voltage and current rating. If the labels do not match, do not install the inverter

module. Each unit will bear a label (examples shown below) on the inverter module

and on the inside chassis floor.

Fig. 1-6, Inverter Module Voltage Rating Labels

Current 36V Inverter Modules bear this yellow label. This

label and the label located on the interior chassis floor must
match. However, inverter modules carrying this yellow label are
backward compatible with 36V power supplies manufactured
prior to September 2006, which bear yellow labels. Do not install
the inverter module if the voltages do not match.

36V

953-527-10-002 F

48VOLT

953-527-11-002 F

1350VA

48V

953-527-12-002 F

Current 48V inverter modules bear this two-color label. This label

and the label located on the interior chassis floor must match.
However, inverter modules carrying this blue/green label are
backward compatible with all 48V power supplies manufactured
prior to September 2006, which bear green labels.

Obsolete-style label for the 1350VA 48V inverter modules.
The current 1350VA 48V inverter module (manufactured after

September 2006) carries a green label. If your legacy power
supply carries this green voltage and current rating label, it is
compatible with the latest blue/green labeled inverter module.

19

017-805-B0-010 Rev. K2

Advertising