2.2 Installing the Optional Indicator Lamps
2.2.1 AC Indicator Lamp
The AC indicator (green lamp) is located on the outside of the enclosure. When lit,
it indicates AC power is available at the power supply output and enables service
personnel to determine the status of the power supply without having to climb the
pole.
Installation Procedure:
1.
Remove the rear-most knockout (see Fig. 2-5).
2. Feed ACI wires through the hole.
3. Slide locking nut over the wires and thread onto lamp body
(see Fig. 2-1).
4. Insert the crimped contacts into the plastic connectors. The BLACK wire must
always go into the BLACK housing. Insert the remaining wire
(this may be white,
yellow or blue) into the WHITE housing (see Fig. 2-2).
5. Connect the shorter BLACK/WHITE set of wires to the BLACK/WHITE wires
leading from the SPI. The remaining set of longer wires connects to the Output
1A connector on the front of the power supply (Fig. 2-5).
Secure the contact. If you do not properly position the contact, overheating and cable
assembly failure can result.
To remove the wire from the plastic housing, use a small screwdriver to depress the metal retainer
and slide out the wire.