3.2

AC Input Voltage Reconfiguration, continued

3.2.2 Reconfiguration from 240 to 120Vac

NEMA 5-20P

(P/N 874-540-20)

NEMA 5-20R

(P/N 531-006-10)

NEMA 6-15P

(P/N 874-540-22)

NEMA6-15R

(P/N 531-004-10)

Fig. 3-6, Typical NEMA Receptacles and Plugs

240V,15A Plug and Receptacle

120V, 20A Plug and Receptacle

Tools Required:

• #2 Phillips head screwdriver
• Flat-blade screwdriver

Supplies Required:

120Vac 20A line cord

(NEMA 5-20P, P/N 874-540-20)

120Vac Input Select Jumper (P/N 744-281-20)

Contact your Alpha Technologies representative for Wire Set part numbers.

Procedure (240Vac Input to 120Vac Input):

1. Completely shut down the XM2 power supply. Remove all utility and battery

power. Remove all connections and cables from the XM2 power supply.

2. Verify the enclosure system wiring before proceeding with power supply

modification. Refer to the appropriate enclosure installation instructions.

3.

Replace the 240Vac 15A line cord (NEMA 6-15P) on the XM2 power supply with

a 120Vac 20A line cord (NEMA 5-20P). Verify proper wiring and ground on the
new plug.

4. Locate the transformer module input jumpers in the transformer compartment.

Replace the currently installed 240Vac jumper (744-281-21) with a 120Vac

jumper (744-281-20) and reconfigure JP1 and JP2 as shown below.

Fig. 3-7, Transformer Module Input Jumpers, PDB Jumpers

120Vac Input Select Jumper

(P/N 744-281-20)

240Vac Input Select Jumper

(P/N 744-281-21)

JP1 & JP2

120

240

JP1 & JP2

120

240

48

017-805-B0-010 Rev. K2