4.3 Smart Display Modes

4.3.1 Operation Normal

If no alarms are present, the power supply operates in Operation Normal display mode.
In this mode you can view the primary operating parameters of the power supply while
the display auto scrolls through the available menu items at two-second intervals.

In Operation Normal mode the displayed items are all “metered” items and are for

informational purposes only (not programmable) with respect to the operational status of
the power supply.

The Operation Normal menu contains the following items:

Fig. 4-4, Operation Normal Display

(Examples are given for values in the display)

The top line indicates the current screen and provides additional instructions. Use the
arrows to manually scroll.

The second line cycles through the parameters listed above.

*

Only visible in single-step mode

*

*

OPERATION NORMAL
OPER MODE =

LINE

INPUT VOLTAGE

120V

INPUT FREqUENCy

60hz

OUTPUT VOLTAGE

89V

OUTPUT 1 CURRENT

12.2A

OUTPUT 2 CURRENT

12.2A

OUTPUT WATTS

900W

OUTPUT VA

1060

PERCENT LOAD

80%

ChARGER MODE =

FLOAT

BATTERy VOLTS

40.5V

BATTERy TEMP

37C

ChARGER CURRENT

8.2A

12 EVENTS

65 MIN

Second line

Top Line