6.0 Specifications

6.1 Intelligent CableUPS North American Models

The following table shows the electrical, mechanical and physical specifications for the North
American models of the Intelligent CableUPS.

Models:

XM2-906HP

XM2-910

XM2-1350-48 XM2-915

XM2-915HV

XM2-922

XM2-922HV

XM2-918HP

XM2-924HP

Electrical

Input Voltage (Vac):

120/240

120/240

120/240

120/240

120/240

208/240

240

120/240

208/240

Input Voltage Window:

-30 to +20%

-20 to +15%

-20 to +15%

-20 to +15%

-30 to +15%

-20 to +15%

-30 to +15%

-20 to +15%

-20 to +15%

Input Frequency:

60Hz

60Hz

60Hz

60Hz

60Hz

60Hz

60Hz

60Hz

60Hz

Input Frequency Window:

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

Output Voltage (Vac):

63/87

63/75/87

63/75/87

63/75/87

63/75/89

63/75/87

63/75/89

63/75/87

63/75/87

Output Current (A):

8/6

10/10/10

22/15/15

15/15/15

20/17.5/15

22/22/22

22/22/22

22/18/18

22/22/24

Max Output Power (VA):

540

900

1350

1350

1350

2025

2025

1620

2160

Output Waveform:

Quasi-square wave

Voltage Regulation

1

:

±5%

±5%

±5%

±5%

±5%

±5%

±5%

±5%

±5%

Output
Frequency
Stability:

Line Mode

60Hz Nominal

Inverter Mode

60Hz, ±0.05%

Short Circuit Protection:

<150% of maximum current rating

Transfer Characteristics:

Uninterrupted output

Battery Voltage (Vdc):

36

36

48

36

36

48

48

36

48

Efficiency
(Typical Load Range)

Line Mode:

80-87%

86-90%

90-92%

Standby Mode:

79-84%

82-85%

84-86%

Battery Charger

Temperature Compensation:

Programmable (0 to 5mV/Cell/°C)

Charger Current:

10A at 80% load and nominal input (bulk charge mode)

Three Stage:

Bulk, Accept, Float

Mechanical

Status Display:

2 x 20 Blue LCD with backlight

Dimensions
H x W x D (in/mm):

8.8 x 15 x 13 / 222 x 381 x 330

Approx. Weight (lb/kg):

53/24

62/28.1

70/31.8

70/31.8

72/32.7

92/41.7

96/43.5

72/32.7

95/42.9

Finish:

Black, epoxy powdercoat

Environment

Operating Temperature:

-40 to 55°C / -40 to 131°F

Relative Humidity:

0 to 95% non-condensing

Agency Compliance:

FCC Part 15 Class A, UL1778, UL1012, CSA 22.2 No. 107.1

Optional Features

Standard Protective Interface Module (PIM/N+1): Provides two programmable outputs from a single XM2 CableUPS power supply for redundancy in critical applications. The PIM
protects system components and provides isolation between distribution legs by shutting down the individual load during over-current conditions.

1

Note: Voltage regulation is maintained over both line and load ranges.

Table 6-1 Specifications for North American Models