6.0 Specifications
6.1 Intelligent CableUPS North American Models
The following table shows the electrical, mechanical and physical specifications for the North
American models of the Intelligent CableUPS.
Models:
XM2-906HP
XM2-910
XM2-1350-48 XM2-915
XM2-915HV
XM2-922
XM2-922HV
XM2-918HP
XM2-924HP
Electrical
Input Voltage (Vac):
120/240
120/240
120/240
120/240
120/240
208/240
240
120/240
208/240
Input Voltage Window:
-30 to +20%
-20 to +15%
-20 to +15%
-20 to +15%
-30 to +15%
-20 to +15%
-30 to +15%
-20 to +15%
-20 to +15%
Input Frequency:
60Hz
60Hz
60Hz
60Hz
60Hz
60Hz
60Hz
60Hz
60Hz
Input Frequency Window:
±3Hz
±3Hz
±3Hz
±3Hz
±3Hz
±3Hz
±3Hz
±3Hz
±3Hz
Output Voltage (Vac):
63/87
63/75/87
63/75/87
63/75/87
63/75/89
63/75/87
63/75/89
63/75/87
63/75/87
Output Current (A):
8/6
10/10/10
22/15/15
15/15/15
20/17.5/15
22/22/22
22/22/22
22/18/18
22/22/24
Max Output Power (VA):
540
900
1350
1350
1350
2025
2025
1620
2160
Output Waveform:
Quasi-square wave
Voltage Regulation
1
:
±5%
±5%
±5%
±5%
±5%
±5%
±5%
±5%
±5%
Output
Frequency
Stability:
Line Mode
60Hz Nominal
Inverter Mode
60Hz, ±0.05%
Short Circuit Protection:
<150% of maximum current rating
Transfer Characteristics:
Uninterrupted output
Battery Voltage (Vdc):
36
36
48
36
36
48
48
36
48
Efficiency
(Typical Load Range)
Line Mode:
80-87%
86-90%
90-92%
Standby Mode:
79-84%
82-85%
84-86%
Battery Charger
Temperature Compensation:
Programmable (0 to 5mV/Cell/°C)
Charger Current:
10A at 80% load and nominal input (bulk charge mode)
Three Stage:
Bulk, Accept, Float
Mechanical
Status Display:
2 x 20 Blue LCD with backlight
Dimensions
H x W x D (in/mm):
8.8 x 15 x 13 / 222 x 381 x 330
Approx. Weight (lb/kg):
53/24
62/28.1
70/31.8
70/31.8
72/32.7
92/41.7
96/43.5
72/32.7
95/42.9
Finish:
Black, epoxy powdercoat
Environment
Operating Temperature:
-40 to 55°C / -40 to 131°F
Relative Humidity:
0 to 95% non-condensing
Agency Compliance:
FCC Part 15 Class A, UL1778, UL1012, CSA 22.2 No. 107.1
Optional Features
Standard Protective Interface Module (PIM/N+1): Provides two programmable outputs from a single XM2 CableUPS power supply for redundancy in critical applications. The PIM
protects system components and provides isolation between distribution legs by shutting down the individual load during over-current conditions.
1
Note: Voltage regulation is maintained over both line and load ranges.
Table 6-1 Specifications for North American Models