3.2

AC Input Voltage Reconfiguration, continued

3.2.1 Reconfiguration from 120 to 240Vac, continued

4.

Locate the transformer module’s input jumper in the transformer compartment.

Replace the currently installed 120Vac jumper (744-281-20) with a 240Vac

jumper (744-281-21).

5.

Remove the five front panel screws. Lift the transformer module front panel up
and away from the chassis. The front handle and output fuse remain in place.

6.

Reconfigure the PDB to 240Vac input, according to Table 3-2.
• Change Switch 2-4 (SW2-4) to ON, Switch 2-5 (SW2-5) to OFF

• Change Switch 2-6 (SW2-6) to ON, Jumper 1 (JP1) to Short (240) and

Jumper 2 (JP2) to Short (240).

7. Replace the front panel.

8. Install the power supply into the enclosure as outlined in Section 2.1 (Installation

Procedure).

Fig. 3-4, Transformer Module Input Jumpers, PDB Jumpers

Fig. 3-5, SW2 Settings

120Vac

Input Select Jumper

(P/N 744-281-20)

240Vac

Input Select Jumper

(P/N 744-281-21)

Only adjust positions SW2 -4, -5, -6. Do not adjust the other switch positions.

NOTE:

JP1 & JP2

120

240

JP1 & JP2

120

240

240Vac

120Vac

ON

4 5 6

Legend

OFF ON

47