1 power distribution board (pdb) setup, continued – Alpha Technologies XM2, XM2-HV, XM2-HP User Manual

Page 43

Advertising
background image

Frequency

60 Hz

50Hz

SW1-8

OFF

ON

Battery Voltage

36Vdc

48Vdc

SW1-7

OFF

OFF

SW1-6

OFF

ON

Power Rating

480VA / 525VA

1

/ 600VA

720VA

2

/ 900VA

1350VA

1620VA

6

/

2000VA / 2160VA

7

SW1-5

ON

OFF

OFF

ON

SW1-4

ON

OFF

ON

OFF

Output Voltage

48Vac

63Vac

75Vac

87Vac

SW1-3

ON

OFF

OFF

ON

SW1-2

ON

OFF

ON

OFF

Output Current

<17A

>17A

SW1-1

OFF

ON

Input Voltage

100Vac

110Vac

120Vac

3

127Vac

200Vac

220Vac

230Vac

240Vac

SW2-6

OFF

ON

OFF

ON

OFF

OFF

ON

ON

SW2-5

OFF

ON

OFF

ON

ON

ON

OFF

OFF

SW2-4

ON

OFF

OFF

ON

OFF

ON

OFF

ON

JP1 & JP2

OPEN

or 120V

OPEN

or 120V

OPEN

or 120V

OPEN

or 120V

SHORT
or 240V

SHORT
or 240V

SHORT
or 240V

SHORT
or 240V

Input

Tolerance

4

Standard and HP models

HV

5

CFR

+15% /–20%

+15% /–30%

+20%

SW2-7

OFF

50Hz or 60Hz

ON

60Hz only

ON

50Hz only

1

525VA applies only to the XM2-906G6 and the XM2-906HP. SW1-5 and SW1-4 must be ON.

2

The output power rating of the XM2-615A when configured for 48V.

3

The XM2-906G5 will display an Input

Voltage of 115Vac when these switches are configured for

120Vac.

4

For HV units, SW2-7 must be changed from OFF to ON when upgrading the inverter module from

firmware v4.00.1 (or lower) to v4.0.1.0. See Alpha Tech Note 017-805-C0 for more information.

5

The XM2-906G6 and XM2-906HP use HV setting and the input tolerance is +20% / –30%.

6

Power rating for the XM2-918HP; supported by Code Version 7.08 and higher.

7

Power rating for the XM2-924 HP; SW1-7 and SW1-6 are both set to ON. Supported by Code

version7.08 and higher.

Table 3-1, Power Distribution Board Setup

3.1

Power Distribution Board (PDB) Setup, continued

ON

SW1 (Output)

SW2 (Input)

All OFF (120Vac)

OFF

Setting for standard
XM2-915, 120Vac,
60Hz and 36Vdc

SW1-3, SW1-4 ON

The table below shows the respective Jumper and
Switch settings for the parameters applicable to
the model of CableUPS in your system.