4.4 Alarm Indications

In the event of a failure, the Active Alarm displays which alarms are active and how to

correct the alarm condition. Major alarms cause the red LED to flash.
• Press UP or DOWN to stop Auto Scroll. Arrows on the right-hand side of the

display text indicate which keys to press to display the next menu item.

• Press UP or DOWN to select the alarm of interest.
• Press ENTER to select the alarm and display diagnostic information. Press

ESCAPE to return to the alarm list.

A Help sub-menu provides possible remedies relating to the active alarm. To access
the Active Alarm Help sub-menu, scroll to the alarm of interest and press ENTER.
The diagnostic information initially auto scrolls. To enter manual scroll mode, press
either UP or DOWN. Press DOWN to scroll through the list of remedies.

Alarms are classified in two categories:

MAJOR Alarms are indications of a serious failure within the CableUPS, such as
a loss of output voltage or a failed battery charger. Any situation that causes output
failure is considered a Major Alarm. Major alarms require immediate action to correct
the failure. To correct major alarms, follow the Smart Display on-screen instructions.

MINOR Alarms indicate a less serious failure, such as defective RTS or loss of utility
power. Corrective action can be delayed for a short time. To correct, follow the Smart
Display on-screen instructions.

The alarm matrices on the following pages indicate the MAJOR/MINOR active
alarms, the probable cause and troubleshooting items to check to correct the alarm
condition.

If only one alarm is active, the alarm list is bypassed and diagnostic information for the single
active alarm displays.

NOTE:

65