Providing Power via Portable Generator or Inverter, continued

4.8.2

AC Powering, continued

4. After the generator is properly grounded, unplug the power supply from the

convenience outlet inside the enclosure and plug the power supply input cable

into the generator output. Use an NEC or UL approved extension cord.

5. Start and operate the generator according to the generator operation manual.

6. If the generator kilowatt rating is twice the kilowatts used by the power supply

indicated on the Smart Display, leave the battery breaker on and the generator
will charge the batteries. If the generator fails, the power supply will continue to

provide battery backup. If the generator output is not approximately twice the
kilowatt rating indicated on the Smart Display, switch the battery breaker off to
reduce the load on the generator if battery backup of the system is unavailable.

7. In either case, after the power from the generator is applied to the power supply,

use the Smart Display to increase the Frequency Input Tolerance to ±6Hz from
the normal ±3Hz, inhibiting the power supply from switching to battery backup
if the generator occasionally does not operate on the proper frequency. It is not

uncommon for smaller (4 kilowatt or less) sized generators to get “off frequency”
due to the step loading of the power supply.

4.8.3 Using a Truck-mounted Inverter or Generator

To use a truck-mounted inverter or generator follow the steps listed in Section
4.8.2 with the additional step of grounding the truck. Run the ground wire from an
unpainted point on the truck chassis to either a driven ground rod or strand ground
to complete the grounding circuit. The rubber tires on the truck insulate it from being

grounded in all but the most exceptional circumstances.

Ground the vehicle before operating a truck inverter or truck-mounted generator.
Failure to do so places service personnel at risk for electric shock.