2.7

Programming the PIM, continued

2.7.1 The Setup Menu

You can also access ON or OFF and YES or NO selections as described above. The
CODE VER, XM_CLASS VER and Total Run Time selections are for informational
display only and cannot be edited.

The SET DEFAULTS menu selection does not reset STANDBY TIME, STANDBY EVENTS or
DEVICE ADDRESS. Manually reset these options.

NOTE:

Press the Enter key to access the Setup Menu.

Use the Setup menu to view or change the programmable operating parameters
of the power supply or the optional PIM. Navigation is similar to the Operation
Normal menu. Press UP or DOWN to access the Single Step mode where you can
individually select sub-menu items.

To select and change a value in the Setup Menu:

1. Press either UP or DOWN to put the display in the Manual Scroll Mode.

2. Continue pressing UP or DOWN until the desired item is displayed.

3. Press ENTER to select the item to edit.

4. Press UP to increase the displayed value or DOWN to decrease the value. To

change the displayed values more rapidly, in Edit mode, press either UP or
DOWN and hold for more than two seconds.

5. Press ENTER when the desired value is displayed. Press ENTER again to

accept and save the new value. To leave programming mode without saving the
new value, press ESCAPE.

If an incorrect value is accidently entered, repeat the above process and enter
the proper value or select the SET DEFAULTS menu selection of the Setup
Menu and press ENTER twice to reset all parameters to their factory default
values.

6. To return to the Operation Normal menu, press ESCAPE three times.