Safety ground and earth connection, Power output return, Communications grounding – Alpha Technologies XM2, XM2-HV, XM2-HP User Manual

Page 13

Advertising
background image

Grounding and Earth Connection Notes

In order to provide a ready, reliable source of backup power it is necessary to connect the power supply to an
effective grounding and Earthing system that not only provides for the safety of the service personnel responsible for
its operation and maintenance, but also facilitates the proper operation and protection of the equipment within the
network. Such a grounding system provides protection with respect to operator safety, system communication and
equipment protection.

Lightning strikes, grid switching or other aberrations on the power line and/or communications cable have the
potential to cause high-energy transients that can damage the powering or communications systems. The most viable
method available to protect the system from damage is to divert these unwanted high-energy transients along a low-
impedance path to Earth. A low-impedance path to Earth prevents these currents from reaching high voltage levels
and posing a threat to equipment.

The key to the success of lightning protection is single-point grounding so the components of the grounding system
appear as a single point of uniform impedance. Two places recommended by Alpha for single-point grounding are
connections in the enclosure and connections to Earth. Single-point grounding in the enclosure is achieved by bonding
all electrical connections to the enclosure, including the connection to Earth, as close together on the enclosure as

possible. Single-point grounding for the connection to Earth is achieved, for example by the proper bonding of the
ground rods.

Safety Ground and Earth Connection

The safety ground and Earth is a two-part system, comprised of the utility service and the Alpha system.

1. First, utility service;

As a minimum requirement for the protection of Alpha equipment, the local utility service must provide a low-
impedance path for fault current return. In addition, there must be a low impedance bonded path between the Alpha
Power Supply power plug Ground Pin and the Enclosure.

2. Second, the Alpha grounding system;

The Alpha grounding system consists of a low-impedance connection between the enclosure and an Earth Ground

(located at least 6’ away from the Utility Earth connection).
This impedance between the enclosure and Earth must be 25 Ohms or less at 60 Hertz as measured by AMPROBE

Model DGC-1000 or equivalent. The measurement should be made on the wire or ground rod after it exits the
enclosure.

Local soil conditions will determine the complexity of the grounding system required to meet the 25 Ohm (maximum)

resistance specified above. For example, a single 8’ ground rod may be sufficient to meet the requirement. In
some cases, a more elaborate system may be required such as multiple ground rods connected by a #6AWG solid

copper cable buried 8-12” below the surface. Where this is not possible, contact a local grounding system expert for

alternate methods that will meet the 25 Ohm (maximum) specification.

All ground rod connections must be made by means of a listed grounding clamp suitable for direct burial or
exothermic welding.

Power Output Return

For proper operation, the Service Power Inserter (SPI) must be securely bonded to the enclosure.

Communications Grounding

For an external status monitoring transponder, the transponder chassis is typically bonded via a separate ground wire
to the enclosure. For systems using an embedded transponder, the grounding connection is typically made either
through a separate chassis ground block bonded to the enclosure or by means of the internal mounting hardware
which bonds the transponder through the CableUPS. Please refer to the appropriate communications product manual
for installation procedures.

Alpha strongly recommends on communication cables the use of a surge arresting device electrically bonded to the
Alpha Enclosure.

Low impedance grounding is mandatory for personnel safety and critical for the
proper operation of the cable system.

WARNING!

13

017-805-B0-010 Rev. K2

Advertising