6.2 Intelligent CableUPS International Models

The following table shows the electrical, mechanical and physical specifications for the
International models of the Intelligent CableUPS.

XM2 Models:

906HP

906G5

608G5

910

915E

915M

915P

622CE

615CE HP

918HP

Electrical
Input Voltage (Vac):

120/240

115/230

115/230

120/240

190/220/247

100/112/127

190/220/253

230

230

120/240

Input Voltage Window:

-30 to +20%

-30 to +20%

-30 to +20%

-20 to +15%

-20 to +15%

-20 to +15%

-20 to +15%

-20 to +15%

-20 to +15%

-20 to +15%

Input Voltage Window w/ATS:

n/a

n/a

n/a

n/a

-30 to +25%

-30 to +25%

-30 to +25%

n/a

n/a

n/a

Input Frequency:

60Hz

50Hz

50Hz

60Hz

50Hz

60Hz

60Hz

50Hz

50Hz

60Hz

Input Frequency Window:

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

±3Hz

Output Voltage (Vac):

63/87

63/87

63

63/75/87

63/75/87

63/75/87

63/75/87

63/48

63/48

63/75/87

Output Current (A):

8/6

8/6

8

10/10/10

15/15/15

15/15/15

15/15/15

22/22

15/15

22/18/18

Max Output Power (VA):

540

540

540

900

1350

1350

1350

1350

900

1620

Output Waveform:

Quasi-square wave

Voltage Regulation

1

:

±5%

±5%

±5%

±5%

±5%

±5%

±5%

±5%

±5%

±5%

Output

Frequency

Stability:

Line Mode

60Hz Nominal

50Hz Nominal

60Hz Nominal

50Hz Nominal

60Hz Nominal

50Hz Nominal

60Hz Nominal

Inverter Mode

60Hz, ±0.05%

50Hz, ±0.05%

60Hz, ±0.05%

50Hz, ±0.05%

60Hz, ±0.05%

50Hz, ±0.05%

60Hz, ±0.05%

Short Circuit Protection:

<150% of maximum current rating

Transfer Characteristics:

Uninterrupted output

Battery Voltage (Vdc):

36

36

36

36

36

36

36

48

36

36

Efficiency

(Typical Load Range)
Line Mode:

80-87%

86-90%

88-92%

Standby Mode:

79-84%

82-85%

84-86%

Battery Charger
Temperature Compensation:

Programmable (0 to 5mV/Cell/°C)

Charger Current:

10A at 80% load and nominal input (bulk charge mode)

Three Stage:

Bulk, Accept, Float

Mechanical
Status Display:

2 x 20 Blue LCD with backlight

Dimensions H x W x D (in/mm):

8.8 x 15 x 13 / 222 x 381 x 330

Approx. Weight (lb/kg):

53/24

62/28.1

62/28.1

62/28.1

82/37.2

70/31.8

70/31.8

82/37.2

70/31.8

72/32.7

Finish:

Black, epoxy powdercoat

Environment
Operating Temperature:

-40 to 55°C / -40 to 131°F

Relative Humidity:

0 to 95% non-condensing

Agency Compliance
FCC Part 15 Class A,

UL1778, UL1012,

CSA 22.2 No. 107.1:

Yes

-

-

Yes

-

-

-

-

-

Yes

CE, EN50083-2, EN62040-2,

EN60950-1, EN62040-1:

-

-

Yes

-

-

-

-

Yes

Yes

-

CB Scheme, IEC 60950-1, EMC

to CISPR22 Class A:

-

Yes

Yes

-

Yes

2

Yes

Yes

3

-

-

-

Optional Features

Standard Protective Interface Module (PIM/N+1): Provides two programmable outputs from a single XM2 CableUPS power supply for redundancy in critical applications. The PIM

protects system components and provides isolation between distribution legs by shutting down the individual load during over-current conditions.

Five Output Protective Interface Module (PIM): Provides four programmable outputs from a single XM2 CableUPS power supply for protection in centralized powering applications. The PIM protects system components and

provides isolation between distribution legs by shutting down the individual load during over-current conditions. An Optical Network Unit (ONU) output is tied to Output 2.

Automatic Tap Switch (ATS): The ATS extends the input AC operating voltage range as indicated above. The ATS is used when a broader input operating range is needed due to utility voltage fluctuations and is currently

available in XM2-915 E/P/M models. Not used in the United States or Canada.

1

Note: Voltage regulation is maintained over both line and load ranges.

2

Note: Certified to CB Scheme and IEC 60950-1.

3

Note: Available only for XM2-915P-CB models.

Table 6-2 Specifications for International Models

84

017-805-B0-010 Rev. K2

Advertising