Active Alarm or

Abnormal Condition

Probable Causes

Corrective Action

Output 1 Tripped

Output 1 hardware protection
mode engaged
(only active with optional PIM

installed)

1. Over Current
2. Check Settings

Output 1 Tripped

Output 1 hardware protection
mode engaged
(only active with optional PIM

installed)

1. Over Current
2. Check Settings

Charger Failure Alarm

Bad batteries

Inverter Module not seated

Inverter Module failure?

1. Open the Battery Circuit Breaker,
2. Verify the Display is still on.
3. If Display drops out….
4. Pull out the Inverter Module
5. Inspect the Inverter Module and rear

Anderson connectors.

6. Re-seat the Inverter Module
7. Turn the Battery Circuit Breaker back

on.

8. Check charging current on display.
9. Run Self Test (press Down and Enter

simultaneously).

10. Check Battery Voltage.
11. Check Battery physical condition.
12. Wait a minimum of three hours.
13. Check Battery Voltage again.
14. Verify Battery Voltage has increased

(Battery charging) and Alarm has not
returned.

15. Replace Inverter Module

Inverter Disconnected

The Inverter Module is not properly
connected

1. Reseat Inverter Module
2. Check Ribbon Cable

Inverter Temperature

Inverter heatsink has exceeded set
temperature (Standby operations
suspended until temperature drops

to safe level).

1. Check Fan

2. Check Filter (legacy models)

4.4 Alarm Indications, continued

70

017-805-B0-010 Rev. K2