background image

* 100Ah = 1 battery string, 200Ah = 2 battery strings, 300Ah = 3 battery strings
* * Feature not available in US

4.3

Smart Display Modes, continued

4.3.3

Setup Menu, continued

The Setup Menu contains the following items:

Top Line (provides additional information)

• SET UP MENU

TO MANUAL SCROLL

• <ESC> TO COMMS INFO

Second Line (cycles through the following parameters):

See Section 4.6 Smart Display Glossary for descriptions of setup menu parameters.

NOTE:

Default

Minimum

Maximum

Other Battery Types

Other

If AlphaCell™ is selected then user

selects between a range of Alpha cells

Float V/C

2.27 V/C

2.10 V/C

2.35 V/C

Accept V/C

2.40 V/C

2.20 V/C

2.45 V/C

Temp Comp

5.0 mV

0.0 mV

5.0 mV

Batt. Capacity*

100 AH

0

1000 AH

Standby Time

0

0

65335

Standby Events

0

0

65335

Total Runtime

0

0

65335

Self Test

Off

Off

Yes

Test Inhibit

7 Days

7 Days

Test Interval

30 Days

0 Days

360 Days

Test Duration

10 Min

5 Min

180 Min

Test Countdown

0

0

365 Days

Freq. Range

3.0Hz

1.0Hz

6.0Hz

Tap Switch**

No

No

Yes

PIM Option

Yes

No

Yes

Reset Output 1

No

Yes

Reset Output 2

No

Yes

Over Curr1

3.0 A

24 A

Over Curr2

3.0 A

24 A

Retry Delay

60 Sec

5 Sec

301 Sec

Retry Limit

20

0

40

Over Curr Tol

3000ms

20ms

9000ms

N+1 Valid

No

No

Yes

Set Defaults

No

Yes

Language

English

Spanish/French/Portuguese/German

These items
appear in the setup
menu only
if battery type
Other is selected.
They are preset

(but not displayed)
if AlphaCell™ is
selected.

These items
appear in the setup
menu only
if the optional
PIM is installed.