Alpha Technologies XM2, XM2-HV, XM2-HP User Manual

Page 68

Advertising
background image

Active Alarm or

Abnormal Condition

Probable Causes of Alarm

Corrective Action

Low Batt Volts

Bad Batteries or 36 Volt battery string
below 33.0 Vdc or 48 Volt battery string
below 44.0 Vdc, Inverter Module not
seated or AC Input Fail or Inverter
Module Failure

1. Check Battery Voltage and

compare to Displayed Battery
Voltage

2. Check for correct battery capacity

on Set-up Menu.

3. Check for AC Input Voltage present
4. Open the Battery Circuit Breaker

and

5. Pull out the Inverter Module
6. Verify Inverter Module securely

connected.

7. Re-seat the Inverter Module
8. Turn the Battery Circuit Breaker

back on.

9. Replace Inverter Module

High Batt Volts

36 Volt battery string above 45.0Vdc or,
48V battery string above 60.0Vdc

1. Check Charger settings.

No Batteries

Detected the absence of batteries
(alarm inactive when battery

capacity set to 0)

1. Check Battery breaker
2. Check Connections
3. Check battery Fuse

4.4 Alarm Indications, continued

Active Alarm or

Abnormal Condition

Alarm States

Corrective Action

Output Overload

(XM2)

Overload Indication

Current Range

(approx. %)

1. Check Output current on the

display. If Output Current is >
100% of rating, correct overload
conditions.

2. Check the configuration switch

settings on the Power Distribution
Board match those required for the
power supply.

3. Turn all power off, wait 10

seconds, turn all power back on.

4. Check that configuration settings

on display (press UP and Enter

simultaneously) match the

configuration switch settings on
the Power Distribution Board.

5. If PIM option installed, check PIM

limits on display

6. Replace Inverter Module
7. Replace power supply

Alarm, no shutdown

110 to 115%

Alarm, shutdown in 30m

115 to 125%

Alarm, shutdown in 10m

125 to 150%

Alarm, shutdown in 30s

>150%

Alarm, shutdown in <15s

Short circuit

68

017-805-B0-010 Rev. K2