4.4 Alarm Indications, continued

Preliminary

Active Alarm or

Abnormal Condition

Corrective Action

Probable Cause of Alarm

Batt Temp Probe

1. Check Connection
2. Check Sensor

Remote Temp Sensor (RTS) failed or
is not connected

Input Failure

1. Utility Failure
2. Circuit breaker input
3. Input Connections
4. Check 120/240 Jumpers

Utility AC Input has failed

N+1 In Use

1. Check Output Fuse
2. Check Output Connections

Output of CableUPS has failed. Load
has been transferred to N+1 unit

N+1 Fault

1. Verify wiring
2. Check N+1 output

Input voltage was expected on N+1
unit; none detected.

Active Alarm or

Abnormal Condition

Alarm States

Corrective Action

Output Overload

(XM2-918 HP, XM2-924HP)

Overload Indication

Current Range

(approx. %)

1. Check Output current on the

display. If Output Current
is > 100% of rating, correct
overload conditions.

2. Check the configuration

switch settings on the
Power Distribution Board
match those required for
the power supply.

3. Turn all power off, wait 10

seconds, turn all power
back on.

4. Check that configuration

settings on display
(press UP and Enter

simultaneously) match

the configuration switch
settings on the Power
Distribution Board.

5. If PIM option installed,

check PIM limits on display

6. Replace Inverter Module
7. Replace power supply

Alarm, no shutdown

105 to 107.5%

Alarm, shutdown in
30m

107.5 to 112.5%

Alarm, shutdown in
10m

112.5 to 125%

Alarm, shutdown in
30s

>125%

Alarm, shutdown in
<15

Short circuit

69

017-805-B0-010 Rev. K2