4.4 Alarm Indications, continued

Note 1: To clear a Latched Self-Test Fail Alarm, initiate and complete a successful self-test.
Note 2: Remove and replace power supply. Do not try to clear alarm or replace relay while in
service
.

Note 3: The Automatic Tap Switch (ATS) option is not available in units sold in North America or
Europe.

NOTE:

Active Alarm or

Abnormal Condition

Probable Causes

Corrective Action

Self Test Fail

(see Note 1 below)

36 Volt battery string
below 33.0 Vdc

48 Volt battery string
below 44.0 Vdc

Alarm during a Self-Test

Inverter failure has
occurred

Line Isolation Alarm

1. Check/correct other alarms.
2. Check that correct AC Input Voltage is present
3. Check Battery Circuit Breaker
4. Check Battery Fuse, if installed
5. Check Battery condition and voltage
6. In the event that a Self Test Alarm condition

was already present, re-run the Self Test to
clear the alarm.

7. Change Inverter Module
8. Replace Power Supply

Config Error

Configuration Switch
Settings Incorrect

Power Distribution Board
failure

(see Note 2 below)

1. Check the configuration switch & jumper

settings on the Power Distribution Board
match those required for the power supply.

2. Verify the configuration settings on display

(press UP and Enter simultaneously) match

the application and configuration switch
settings on the Power Distribution Board.

3. Check transformer Output Tap setting to

verify the Inverter Module voltage matches
the Transformer Module voltage and voltage
shown on the label of the Inverter Module
matches the voltage of Transformer Module.

4. Check for corrosion on the Power Distribution

Board.

5. Verify Power Distribution Board to Inverter

Module Ribbon Cable and Connectors are
properly connected.

6. Turn all power off, wait 10 seconds, turn all

power back on.

7. Change Inverter Module
8. Replace power supply.

Tap Fuse Fail

Open ATS fuse

(see Note 3 below)

ATS damage

Power Distribution Board
damage

(see Note 2

below)

1. Check/replace fuse on ATS
2. Check for damaged contacts on the ATS

board relay.

3. Check the configuration switch settings on

the Power Distribution Board match those
required for the power supply.

4. Check that configuration settings on display

(press UP and Enter simultaneously) match

the configuration switch settings on the Power
Distribution Board.

5. Turn all power off, wait 10 seconds, turn all

power back on.

6. Replace power supply

66

017-805-B0-010 Rev. K2

Advertising