3 charger operation, Charger modes, 1 theory of operation, continued – Alpha Technologies XM2, XM2-HV, XM2-HP User Manual

Page 17

Advertising
background image

1.1

Theory of Operation, continued

1.1.3 Charger Operation

The Intelligent CableUPS uses a three-stage, temperature-compensated battery
charger. During AC line operation, the inverter winding on the ferroresonant
transformer feeds the charger circuit which provides BULK, ACCEPT and FLOAT
charge voltages to the batteries.

Charger Modes

BULK

charge is a “Constant Current” charge. The maximum current is 10A. As the

charge is returned to the batteries, their voltage increases to a specific threshold

(2.27Vdc per cell). The charger then switches to ACCEPT mode. The BULK charger
mode generally returns the battery charge state to 80 percent of rated battery
capacity.

ACCEPT

charge is a “Constant Voltage” charge. This voltage, 2.40Vdc (adjustable)

per cell, is temperature-compensated to ensure longer battery life and proper
completion of the charge cycle. This cycle is complete when the charging current into

the batteries becomes less than 0.5A or approximately six hours elapses from the
time ACCEPT mode was entered. When the batteries are fully recharged the charger
switches to the FLOAT mode of operation.

FLOAT

charge is a temperature-compensated “pulsed voltage” charge, averaging

about 2.27Vdc (adjustable) per cell. During FLOAT mode, the batteries are
fully charged and ready to provide backup power. The charger provides a small
maintenance charge to overcome the batteries self-discharge characteristics and

other minor DC loads within the power supply. As the battery voltage reaches the “full

charge” level the time delay between pulses increases.

During ACCEPT and FLOAT modes, the cell voltage is temperature-compensated

at -0.005Vdc per cell per degree C (adjustable) to ensure a safe battery cell voltage

and to maximize battery life.

Fig. 1-4, Charger Modes

(dashed lines indicate HV models)

1

2

3

4

5

6

7

8

9

10

2.15

2.25

2.05

2.40

0

Volts Per Cell

Charger Current

Bulk Accept Float

NOTE:

On HP models, when Alpha Cell is the selected battery type, ACCEPT and FLOAT are pre-set and are
not manually selectable.

17

017-805-B0-010 Rev. K2