Removal Procedure:

1. Turn off the battery breaker.

2. Disconnect the battery input and temp probe cables

from the inverter module and the TMPR and XPDR
cables from the communication module.

3. Loosen the thumbscrews.

4. Grasp the handle on the right side of the inverter

module. Pull firmly to release the module from the
inverter connector. Gently slide the module assembly
straight out until the inverter module ribbon cable
connector is accessible. Move the retaining clips
apart and the ribbon cable will come free from the
connector.

2.4 Inverter Module Removal and Installation

The Intelligent CableUPS comes with a field-replaceable inverter module assembly containing
the inverter and control logic. The inverter module accepts optional communications modules
to facilitate remote status monitoring. The removable module is located on the front, right-
hand side of the unit.

Fig. 2-6, Inverter Module Ribbon Cable

Fig. 2-7, Detail of Locking Mechanism

Disconnect here

ALWAYS switch the battery breaker off before removing or installing the inverter module
assembly.

Handle the inverter module with extreme care. Circuit boards and logic upgrades are static-
sensitive and susceptible to damage.

You can remove the inverter module assembly while the power supply is running on line power. The
power supply will continue to operate as a non-voltage regulated power supply.

NOTE:

Installation Procedure:

1. Reconnect the inverter module ribbon cable

to the Inverter Module circuit board by seating
the cable into the connector (the locking tabs

will automatically engage). Engage the sheet
metal in the upper and lower guides and slide
the inverter module back onto the connector. It
is important the sheet metal is properly seated
in the card guides and fully inserted into the
housing.

2. Tighten the thumbscrews.

3. Verify the battery breaker is off. Reconnect the

battery input, temp probe cables, TMPR and
XPDR cables. Turn the battery breaker on.