G00 setpoint generator - 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 30

G00
SETPOINT GENERATOR - 0
NAME SYMBOL
DATAPOINT
INPUTS
REMOTE SETPOINT
RSP0
C120
REMOTE SP ENABLE
RE0
L115
SETPOINT TRACK INPUT
STV0
C128
SETPOINT TRACK SWITCH
SWSPT0
L116
PARAMETERS
SETPOINT TRACK ENABLE
STE0
L118
REMOTE GAIN
K10
C113
REMOTE BIAS
B10
C112
INSTRUMENT RANGE
IR0
C115
SETPOINT HI LIMIT
SH0
C125
SETPOINT LOW LIMIT
SL0
C126
OUTPUTS
SETPOINT SP0
C101
SETPOINT TRACK STATUS
SPTS0
L104
REMOTE STATUS
RMT0
L108
Description:
This subroutine selects one of three signals to load into SP. The signal selected is
either the Setpoint Track Value (STV), the Remote Setpoint (RSP) after being
multiplied by K1 and biased by B1 or the Setpoint Pushbutton Value. If the Setpoint
Track Switch (SWSPT) is zero (0) then SP = STV when Setpoint Tracking is enabled
(STE=1). When the previous condition is not in effect SP will equal (RSP x K1) + B1
if Remote Enable = 1 and the R/L pushbutton has set the Remote Switch to 1. When
none of the previous conditions are in effect the signal comes directly from the
setpoint increase and decrease pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-23