G11 pid - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 41

Advertising
background image

G11
PID - 3

NAME

SYMBOL

DATAPOINT

INPUTS

PROCESS VARIABLE

PV3

C208

DEVIATION

DV3

C229

RESET FEEDBACK

RF3

C235

CONTROL TRACK
COMMAND

CTC3

L195

PARAMETERS

PROPORTIONAL BAND

PB3

C214

RESET TIME

TR3

C215

RATE TIME

TD3

C216

OUTPUT HIGH LIMIT

OH3

C217

OUTPUT LOW LIMIT

OL3

C218

MANUAL RESET

MR3

C219

INSTRUMENT RANGE

IR3

C223

FEED FORWARD

FF3

C230

REVERSE SWITCH

RSW3

L178

OUTPUTS

CONTROL OUTPUT

CO3

C231

Description:
This subroutine computes a control output signal based on the above listed inputs
and parameters. The result is available as a database parameter CO. When the
control track command is zero,the module output will track the reset feedback by
back calculating the integrator term. When CTC is 1, the reset feedback is used by
the integrator to calculate the next output and should reflect the value (scaled
0-100%) of the value of the final control element. For standard PID controller
operation, reset feedback should equal OUT and control track command should
equal AUT.