G11 pid - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 41

G11
PID - 3
NAME
SYMBOL
DATAPOINT
INPUTS
PROCESS VARIABLE
PV3
C208
DEVIATION
DV3
C229
RESET FEEDBACK
RF3
C235
CONTROL TRACK
COMMAND
CTC3
L195
PARAMETERS
PROPORTIONAL BAND
PB3
C214
RESET TIME
TR3
C215
RATE TIME
TD3
C216
OUTPUT HIGH LIMIT
OH3
C217
OUTPUT LOW LIMIT
OL3
C218
MANUAL RESET
MR3
C219
INSTRUMENT RANGE
IR3
C223
FEED FORWARD
FF3
C230
REVERSE SWITCH
RSW3
L178
OUTPUTS
CONTROL OUTPUT
CO3
C231
Description:
This subroutine computes a control output signal based on the above listed inputs
and parameters. The result is available as a database parameter CO. When the
control track command is zero,the module output will track the reset feedback by
back calculating the integrator term. When CTC is 1, the reset feedback is used by
the integrator to calculate the next output and should reflect the value (scaled
0-100%) of the value of the final control element. For standard PID controller
operation, reset feedback should equal OUT and control track command should
equal AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-34