F-cim 61 pid - 2 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 69

F-CIM 61
PID - 2
NOT REUSABLE
NAME
SYMBOL
DATAPOINT
INPUTS
S
n-1
DEVIATION
DV2
C193
A
[unused]
B
RESET FEEDBACK
RF2
C199
C
CONTROL TRACK COM-
MAND
CTC2
L171
PARAMETERS
PROPORTIONAL BAND
PB2
C178
RESET TIME
TR2
C179
RATE TIME
TD2
C180
OUTPUT HIGH LIMIT
OH2
C181
OUTPUT LOW LIMIT
OL2
C182
MANUAL RESET
MR2
C183
INSTRUMENT RANGE
IR2
C187
FEED FORWARD
FF2
C194
REVERSE SWITCH
RSW2
L154
OUTPUTS
S
n
CONTROL OUTPUT
CO2
C195
Description:
This module computes a control output signal based on the above listed inputs and parameters.
The result is simultaneously available as the module output S
n
and as a database parameter
CO. The A, B, and C inputs can be any L,B, C[S], or H type datapoint. When the
control track command input is less than one, the module output will track the reset
feedback input (B)by back calculating the integrator term. When (C) input is greater
than or equal to 1 the reset feedback is used by the integrator to calculate the next
output and should reflect the value (scaled 0-100%) of the value of the final control
element. For standard PID controller reset feedback, (B) should be OUT and con-
trol track command should be AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-17