F-cim 47 deviation/alarm calculation - 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 63

F-CIM 47
DEVIATION/ALARM CALCULATION - 0
NOT REUSABLE
INPUTS
NAME
SYMBOL
DATAPOINT
S
n-1
SETPOINT
SP0
C101
A
PROCESS VARIABLE
PV0
C100
PARAMETERS
SETPOINT SLEW RATE
T10
C117
CONTROL ZONE
C20
C114
ALARM INDEX
AIX0
B335
ALARM LIMIT 1
PL10
C103
ALARM LIMIT 2
PL20
C104
ALARM DEADBAND
ADB0
C105
OUTPUTS
S
n
DEVIATION
DV0
C121
ALARM A
PA10
L110
ALARM B
PA20
L111
TRUE SETPOINT
TSP0
C119
Description:
This module calculates and loads the deviation value based on setpoint (S
n
) and
process variable (A). Before the calculation is performed the setpoint value is con-
ditioned so as not to exceed the rate of change limit specified by T1. If the calcu-
lated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and
ADB. Results of the alarm tests are loaded to PA1 and PA2. Refer to Section
4.1.6 of Instruction Bulletin 53MC5000 for an explanation of AIX values.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-11