F-cim 57 deviation/alarm calculation - 1 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 68

F-CIM 57
DEVIATION/ALARM CALCULATION - 1
NOT REUSABLE
INPUTS
NAME
SYMBOL
DATAPOINT
S
n-1
SETPOINT
SP1
C137
A
PROCESS VARIABLE
PV1
C136
PARAMETERS
SETPOINT SLEW RATE
T11
C153
CONTROL ZONE
C21
C150
ALARM INDEX
AIX1
B340
ALARM LIMIT 1
PL11
C139
ALARM LIMIT 2
PL21
C140
ALARM DEADBAND
ADB1
C141
OUTPUTS
S
n
DEVIATION
DV1
C157
ALARM A
PA11
L134
ALARM B
PA21
L135
TRUE SETPOINT
TSP1
C155
Description:
This module calculates and loads the deviation value based on setpoint (S
n
) and
process variable (A). Before the calculation is performed the setpoint value is con-
ditioned so as not to exceed the rate of change limit specified by T1. If the calcu-
lated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and
ADB. Results of the alarm tests are loaded to PA1 and PA2. Refer to Section
4.1.6 of Instruction Bulletin 53MC5000 for an explanation of AIX values.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-16