G09 pid - 1 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 39

G09
PID - 1
NAME
SYMBOL
DATAPOINT
INPUTS
PROCESS VARIABLE
PV1
C136
DEVIATION
DV1
C157
RESET FEEDBACK
RF1
C163
CONTROL TRACK
COMMAND
CTC1
L147
PARAMETERS
PROPORTIONAL BAND
PB1
C142
RESET TIME
TR1
C143
RATE TIME
TD1
C144
OUTPUT HIGH LIMIT
OH1
C145
OUTPUT LOW LIMIT
OL1
C146
MANUAL RESET
MR0
C147
INSTRUMENT RANGE
IR1
C151
FEED FORWARD
FF1
C158
REVERSE SWITCH
RSW1
L130
OUTPUTS
CONTROL OUTPUT
CO1
C159
Description:
This subroutine computes a control output signal based on the above listed inputs
and parameters. The result is available as a database parameter CO. When the
control track command is zero,the module output will track the reset feedback by
back calculating the integrator term. When CTC is 1, the reset feedback is used by
the integrator to calculate the next output and should reflect the value (scaled
0-100%) of the value of the final control element. For standard PID controller
operation, reset feedback should equal OUT and control track command should
equal AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-32