G08 pid - 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 38

G08
PID - 0
NAME
SYMBOL
DATAPOINT
INPUTS
PROCESS VARIABLE
PV0
C100
DEVIATION
DV0
C121
RESET FEEDBACK
RF0
C127
CONTROL TRACK
COMMAND
CTC0
L123
PARAMETERS
PROPORTIONAL BAND
PB0
C106
RESET TIME
TR0
C107
RATE TIME
TD0
C108
OUTPUT HIGH LIMIT
OH0
C109
OUTPUT LOW LIMIT
OL0
C110
MANUAL RESET
MR0
C111
INSTRUMENT RANGE
IR0
C115
FEED FORWARD
FF0
C122
REVERSE SWITCH
RSW0
L106
OUTPUTS
CONTROL OUTPUT
CO0
C123
Description:
This subroutine computes a control output signal based on the above listed inputs
and parameters. The result is available as a database parameter CO. When the
control track command is zero,the module output will track the reset feedback by
back calculating the integrator term. When CTC is 1, the reset feedback is used by
the integrator to calculate the next output and should reflect the value (scaled
0-100%) of the value of the final control element. For standard PID controller
operation, reset feedback should equal OUT and control track command should
equal AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-31