G14 auto/manual switch - 2 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 44

G14
AUTO/MANUAL SWITCH - 2
INPUTS
NAME
SYMBOL
DATAPOINT
CONTROL OUTPUT
CO2
C195
AUTO ENABLE
AE2
L162
OUTPUT TRACK VALVE
OTV2
C201
OUTPUT TRACK SWITCH
SWOTV2
L165
PARAMETERS
OUTPUT TRACK ENABLE
OTE2
L167
HARD MANUAL LIMIT
HML2
L170
OUTPUT HIGH LIMIT
OH2
C181
OUTPUT LOW LIMIT
OL2
C182
OUTPUT SLEW RATE
T32
C190
OUTPUTS
OUTPUT
OUT2
C174
OUTPUT TRACK STATUS
OVTS2
L153
AUTO STATUS
AUT2
L155
Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-37