F-cim 77 deviation/alarm calculation - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 77

F-CIM 77
DEVIATION/ALARM CALCULATION - 3
NOT REUSABLE
INPUTS
NAME
SYMBOL
DATAPOINT
S
n-1
SETPOINT
SP3
C209
A
PROCESS VARIABLE
PV3
C208
PARAMETERS
SETPOINT SLEW RATE
T13
C225
CONTROL ZONE
C23
C222
ALARM INDEX
AIX3
B350
ALARM LIMIT 1
PL13
C211
ALARM LIMIT 2
PL23
C212
ALARM DEADBAND
ADB3
C213
OUTPUTS
S
n
DEVIATION
DV3
C229
ALARM A
PA13
L182
ALARM B
PA23
L183
TRUE SETPOINT
TSP3
C227
Description:
This module calculates and loads the deviation value based on setpoint (S
n
) and
process variable (A). Before the calculation is performed the setpoint value is con-
ditioned so as not to exceed the rate of change limit specified by T1. If the calcu-
lated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and
ADB. Results of the alarm tests are loaded to PA1 and PA2. Refer to Section
4.1.6 of Instruction Bulletin 53MC5000 for an explanation of AIX values.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-25