G13 auto/manual switch - 1 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 43

G13
AUTO/MANUAL SWITCH - 1
INPUTS
NAME
SYMBOL
DATAPOINT
CONTROL OUTPUT
CO1
C159
AUTO ENABLE
AE1
L138
OUTPUT TRACK VALVE
OTV1
C165
OUTPUT TRACK SWITCH
SWOTV1
L141
PARAMETERS
OUTPUT TRACK ENABLE
OTE1
L143
HARD MANUAL LIMIT
HML1
L146
OUTPUT HIGH LIMIT
OH1
C145
OUTPUT LOW LIMIT
OL1
C146
OUTPUT SLEW RATE
T31
C154
OUTPUTS
OUTPUT
OUT1
C138
OUTPUT TRACK STATUS
OVTS1
L129
AUTO STATUS
AUT1
L131
Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-36