F-cim 51 pid - 1 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 64

F-CIM 51
PID - 1
NOT REUSABLE
NAME
SYMBOL
DATAPOINT
INPUTS
S
n-1
DEVIATION
DV1
C157
A
[unused]
B
RESET FEEDBACK
RF1
C163
C
CONTROL TRACK COM-
MAND
CTC1
L147
PARAMETERS
PROPORTIONAL BAND
PB1
C142
RESET TIME
TR1
C143
RATE TIME
TD1
C144
OUTPUT HIGH LIMIT
OH1
C145
OUTPUT LOW LIMIT
OL1
C146
MANUAL RESET
MR0
C147
INSTRUMENT RANGE
IR1
C151
FEED FORWARD
FF1
C158
REVERSE SWITCH
RSW1
L130
OUTPUTS
S
n
CONTROL OUTPUT
CO1
C159
Description:
This module computes a control output signal based on the above listed inputs and parameters.
The result is simultaneously available as the module output Sn and as a database parameter CO.
The A, B, and C inputs can be any L,B, C[S], or H type datapoint. When the control track command
input is less than one, the module output will track the reset feedback input (B) by back calculating
the integrator term. When (C) input is greater than or equal to 1 the reset feedback is used by the
integrator to calculate the next output and should reflect the value (scaled 0-100%) of the value of
the final control element. For standard PID controller reset feedback, (B) should be OUT and con-
trol track command should be AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE