F-CIM 101

MATH B

NOT REUSABLE

Function:

C

S

n

0

S

n-1

1

C79 * S

n-1

+ C80

2

C79 * S

n-1

+ C80 * A + C81 * B

3

C79 * S

n-1

* A * B + C80

4

C79

Sn−1

A

+ C80*B

5

C79 * S

n-1

+

C80

A

B

+ C81

6

C79

Sn−1∗

A

B

+ C80

7

C79

+Sn−1

C80

+A

* C81

8

C79 * ABS(S

n-1

) + C80

9

C79 * S

n-1

(C80 * A + C81)

10

C79 * 2

(C80 * Sn-1 + C81)

11

C79 * LOG (C80 * S

n-1

) + C81

20

C79 < S

n-1

< C80

21

(C80 * B) < S

n-1

< (C81 * A)

Description:

This module provides 12 different mathematical functions. The function to be used is selected
based on the C input.