G01 setpoint generator - 1 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual

Page 31

Advertising
background image

G01
SETPOINT GENERATOR - 1

NAME SYMBOL

DATAPOINT

INPUTS

REMOTE SETPOINT

RSP1

C156

REMOTE SP ENABLE

RE1

L139

SETPOINT TRACK INPUT

STV1

C164

SETPOINT TRACK SWITCH

SWSPT1

L140

PARAMETERS

SETPOINT TRACK ENABLE

STE1

L142

REMOTE GAIN

K11

C149

REMOTE BIAS

B11

C148

INSTRUMENT RANGE

IR1

C151

SETPOINT HI LIMIT

SH1

C161

SETPOINT LOW LIMIT

SL1

C162

OUTPUTS

SETPOINT SP1

L137

SETPOINT TRACK STATUS

SPTS1

L128

REMOTE STATUS

RMT1

L132

Description:
This subroutine selects one of three signals to load into SP. The signal selected is
either the Setpoint Track Value (STV), the Remote Setpoint (RSP) after being
multiplied by K1 and biased by B1 or the Setpoint Pushbutton Value. If the Setpoint
Track Switch (SWSPT) is zero (0) then SP = STV when Setpoint Tracking is enabled
(STE=1). When the previous condition is not in effect SP will equal (RSP x K1) + B1
if Remote Enable = 1 and the R/L pushbutton has set the Remote Switch to 1. When
none of the previous conditions are in effect the signal comes directly from the
setpoint increase and decrease pushbuttons.

MODULAR CONTROLLER CUSTOMIZATION GUIDE

2-24