G01 setpoint generator - 1 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 31

G01
SETPOINT GENERATOR - 1
NAME SYMBOL
DATAPOINT
INPUTS
REMOTE SETPOINT
RSP1
C156
REMOTE SP ENABLE
RE1
L139
SETPOINT TRACK INPUT
STV1
C164
SETPOINT TRACK SWITCH
SWSPT1
L140
PARAMETERS
SETPOINT TRACK ENABLE
STE1
L142
REMOTE GAIN
K11
C149
REMOTE BIAS
B11
C148
INSTRUMENT RANGE
IR1
C151
SETPOINT HI LIMIT
SH1
C161
SETPOINT LOW LIMIT
SL1
C162
OUTPUTS
SETPOINT SP1
L137
SETPOINT TRACK STATUS
SPTS1
L128
REMOTE STATUS
RMT1
L132
Description:
This subroutine selects one of three signals to load into SP. The signal selected is
either the Setpoint Track Value (STV), the Remote Setpoint (RSP) after being
multiplied by K1 and biased by B1 or the Setpoint Pushbutton Value. If the Setpoint
Track Switch (SWSPT) is zero (0) then SP = STV when Setpoint Tracking is enabled
(STE=1). When the previous condition is not in effect SP will equal (RSP x K1) + B1
if Remote Enable = 1 and the R/L pushbutton has set the Remote Switch to 1. When
none of the previous conditions are in effect the signal comes directly from the
setpoint increase and decrease pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-24