G04

DEVIATION/ALARM CALCULATION - 0

INPUTS

NAME

SYMBOL

DATAPOINT

SETPOINT

SP0

C101

PROCESS VARIABLE

PV0

C100

PARAMETERS

SETPOINT SLEW RATE

T10

C117

CONTROL ZONE

CZ0

C114

ALARM INDEX

AIX0

B335

ALARM LIMIT 1

PL10

C103

ALARM LIMIT 2

PL20

C104

ALARM DEADBAND

ADB0

C105

OUTPUTS

DEVIATION

DV0

C121

ALARM A

PA10

L110

ALARM B

PA20

L111

Description:
This subroutine calculates and loads the deviation value based on setpoint (SP) and
process variable (PV). Before the calculation is performed the setpoint value is
conditioned so as not to exceed the rate of change limit specified by T1. If the
calculated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and ADB.
Results of the alarm tests are loaded to PA1 and PA2. Refer to Section 4.1.6 of
Instruction Bulletin 53MC5000 for an explanation of AIX values.