G04
DEVIATION/ALARM CALCULATION - 0
INPUTS
NAME
SYMBOL
DATAPOINT
SETPOINT
SP0
C101
PROCESS VARIABLE
PV0
C100
PARAMETERS
SETPOINT SLEW RATE
T10
C117
CONTROL ZONE
CZ0
C114
ALARM INDEX
AIX0
B335
ALARM LIMIT 1
PL10
C103
ALARM LIMIT 2
PL20
C104
ALARM DEADBAND
ADB0
C105
OUTPUTS
DEVIATION
DV0
C121
ALARM A
PA10
L110
ALARM B
PA20
L111
Description:
This subroutine calculates and loads the deviation value based on setpoint (SP) and
process variable (PV). Before the calculation is performed the setpoint value is
conditioned so as not to exceed the rate of change limit specified by T1. If the
calculated deviation falls within the CZ value, then deviation is forced to 0.0. This
module also determines if alarm conditions exist based on AIX, PL1, PL2 and ADB.
Results of the alarm tests are loaded to PA1 and PA2. Refer to Section 4.1.6 of
Instruction Bulletin 53MC5000 for an explanation of AIX values.