1 statements, 2 assignment statements, 3 conditional statements – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 50: 4 if statements

2.7.1 Statements
Composed of operands and expressions
2.7.2 Assignment Statements
NOTE: In cases where the right side of the statement is a different type
than the left side, the instrument will truncate or expand the
right side to make it compatible.
B operand = < B expression > | < C expression > | < H expression > | < L expression >
C operand = < C expression > | < B expression > | < H expression > | < L expression >
H operand = < H expression > | < C expression > | < B expression > | < L expression >
L operand = < L expression > | < B expression > | < C expression > | < H expression >
A operand = < A expression > | < F expression >
F operand = < F expression > | < A expression >
2.7.3 Conditional Statements
1) < Logical expression > Sxxx
2) < B expression > < B expression > Sxxx
3) < C expression > < C expression > Sxxx
4) < H expression > < H expression > Sxxx
2.7.4 IF Statements
IF
< logical expression >
{
}
ELSE (optional)
{
}
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-43