F-cim 53 auto/manual switch - 1, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 66

F-CIM 53
AUTO/MANUAL SWITCH - 1
NOT REUSABLE
INPUTS
NAME
SYMBOL
DATAPOINT
S
n-1
CONTROL OUTPUT
CO1
C159
A
AUTO ENABLE
AE1
L138
B
OUTPUT TRACK VALVE
OTV1
C165
C
OUTPUT TRACK SWITCH
SWOTV1
L141
PARAMETERS
OUTPUT TRACK ENABLE
OTE1
L143
HARD MANUAL LIMIT
HML1
L146
OUTPUT HIGH LIMIT
OH1
C145
OUTPUT LOW LIMIT
OL1
C146
OUTPUT SLEW RATE
T31
C154
OUTPUTS
S
n
OUTPUT
OUT1
C138
OUTPUT TRACK STATUS
OVTS1
L129
AUTO STATUS
AUT1
L131
Description:
This module selects one of three signals to load into OUT and become its output
(S
n
). The signal selected is either the Output Tracking Value (B), the Auto Value
(S
n-1
) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less
than 1, then S
n
= B when Output Tracking is enabled (OTE = 1). When the pre-
vious condition is not in effect S
n
will equal S
n-1
if Auto Enable (A) is
≥ 1 and the
A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-14