F-cim 71 pid - 3 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 74

F-CIM 71
PID - 3
NOT REUSABLE
NAME
SYMBOL
DATAPOINT
INPUTS
S
n-1
DEVIATION
DV3
C229
A
[unused]
B
RESET FEEDBACK
RF3
C235
C
CONTROL TRACK COM-
MAND
CTC3
L195
PARAMETERS
PROPORTIONAL BAND
PB3
C214
RESET TIME
TR3
C215
RATE TIME
TD3
C216
OUTPUT HIGH LIMIT
OH3
C217
OUTPUT LOW LIMIT
OL3
C218
MANUAL RESET
MR3
C219
INSTRUMENT RANGE
IR3
C223
FEED FORWARD
FF3
C230
REVERSE SWITCH
RSW3
L178
OUTPUTS
S
n
CONTROL OUTPUT
CO3
C231
Description:
This module computes a control output signal based on the above listed inputs and parameters.
The result is simultaneously available as the module output S
n
and as a database parameter
CO. The A, B, and C inputs can be any L,B, C[S], or H type datapoint. When the
control track command input is less than one, the module output will track the reset
feedback input (B) by back calculating the integrator term. When (C) input is
greater than or equal to 1 the reset feedback is used by the integrator to calculate
the next output and should reflect the value (scaled 0-100%) of the value of the fi-
nal control element. For standard PID controller reset feedback, (B) should be OUT
and control track command should be AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-22