F-cim 44 setpoint generator - 0 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 62

F-CIM 44
SETPOINT GENERATOR - 0
NOT REUSABLE
NAME
SYMBOL
DATAPOINT
INPUTS
S
n-1
REMOTE SETPOINT
RSP0
C120
A
REMOTE SP ENABLE
RE0
L115
B
SETPOINT TRACK INPUT
STV0
C128
C
SETPOINT TRACK SWITCH
SWSPT0
L116
PARAMETERS
SETPOINT TRACK ENABLE
STE0
L118
REMOTE GAIN
K10
C113
REMOTE BIAS
B10
C112
INSTRUMENT RANGE
IR0
C115
SETPOINT HI LIMIT
SH0
C125
SETPOINT LOW LIMIT
SL0
C126
OUTPUTS
S
n
SETPOINT
SP0
C101
SETPOINT TRACK STATUS
SPTS0
L104
REMOTE STATUS
RMT0
L108
REMOTE SWITCH
SWR0
L113
Description:
This module selects one of three signals to load into SP and become its output (Sn). The signal se-
lected is either the Setpoint Tracking Value (B), the Remote Setpoint Value (Sn-1) multiplied by K1
and biased by B1, or the Setpoint pushbutton value. If the Setpoint Track Switch (C) is less than 1,
then Sn=B when Setpoint Tracking is enabled (STE=1). When the previous condition is not in ef-
fect Sn will equal Sn-1 x K1 + B1 if RemoteEnable (A) is greater than or equal to 1 and the R/L
pushbutton has set Remote Switch to1. When none of the previous conditions are in effect the se-
lected signal comes directly from the setpoint increase and decrease pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-10