F-cim 64 setpoint generator - 2, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 72

F-CIM 64
SETPOINT GENERATOR - 2
NOT REUSABLE
NAME
SYMBOL
DATAPOINT
INPUTS
S
n-1
REMOTE SETPOINT
RSP2
C192
A
REMOTE SP ENABLE
RE2
L163
B
SETPOINT TRACK INPUT
STV2
C200
C
SETPOINT TRACK SWITCH
SWSPT2
L164
PARAMETERS
SETPOINT TRACK ENABLE
STE2
L166
REMOTE GAIN
K12
C185
REMOTE BIAS
B12
C184
INSTRUMENT RANGE
IR2
C187
SETPOINT HI LIMIT
SH2
C197
SETPOINT LOW LIMIT
SL2
C198
OUTPUTS
S
n
SETPOINT
SP2
C173
SETPOINT TRACK STATUS
SPTS2
L152
REMOTE STATUS
RMT2
L156
REMOTE SWITCH
SWR2
L161
Description:
This module selects one of three signals to load into SP and become its output
(S
n
). The signal selected is either the Setpoint Tracking Value (B), the Remote
Setpoint Value (S
n-1
) multiplied by K1 and biased by B1, or the Setpoint pushbut-
ton value. If the Setpoint Track Switch (C) is less than 1, then Sn=B when Set-
point Tracking is enabled (STE=1). When the previous condition is not in effect S
n
will equal S
n-1
x K1 + B1 if RemoteEnable (A) is greater than or equal to 1 and the
R/L pushbutton has set Remote Switch to1. When none of the previous conditions
are in effect the selected signal comes directly from the setpoint increase and de-
crease pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-20