F-CIM 64
SETPOINT GENERATOR - 2

NOT REUSABLE

NAME

SYMBOL

DATAPOINT

INPUTS

S

n-1

REMOTE SETPOINT

RSP2

C192

A

REMOTE SP ENABLE

RE2

L163

B

SETPOINT TRACK INPUT

STV2

C200

C

SETPOINT TRACK SWITCH

SWSPT2

L164

PARAMETERS

SETPOINT TRACK ENABLE

STE2

L166

REMOTE GAIN

K12

C185

REMOTE BIAS

B12

C184

INSTRUMENT RANGE

IR2

C187

SETPOINT HI LIMIT

SH2

C197

SETPOINT LOW LIMIT

SL2

C198

OUTPUTS

S

n

SETPOINT

SP2

C173

SETPOINT TRACK STATUS

SPTS2

L152

REMOTE STATUS

RMT2

L156

REMOTE SWITCH

SWR2

L161

Description:
This module selects one of three signals to load into SP and become its output
(S

n

). The signal selected is either the Setpoint Tracking Value (B), the Remote

Setpoint Value (S

n-1

) multiplied by K1 and biased by B1, or the Setpoint pushbut-

ton value. If the Setpoint Track Switch (C) is less than 1, then Sn=B when Set-
point Tracking is enabled (STE=1). When the previous condition is not in effect S

n

will equal S

n-1

x K1 + B1 if RemoteEnable (A) is greater than or equal to 1 and the

R/L pushbutton has set Remote Switch to1. When none of the previous conditions
are in effect the selected signal comes directly from the setpoint increase and de-
crease pushbuttons.