G10 pid - 2 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 40

G10
PID - 2
NAME
SYMBOL
DATAPOINT
INPUTS
PROCESS VARIABLE
PV2
C172
DEVIATION
DV2
C193
RESET FEEDBACK
RF2
C199
CONTROL TRACK
COMMAND
CTC2
L171
PARAMETERS
PROPORTIONAL BAND
PB2
C178
RESET TIME
TR2
C179
RATE TIME
TD2
C180
OUTPUT HIGH LIMIT
OH2
C181
OUTPUT LOW LIMIT
OL2
C182
MANUAL RESET
MR2
C183
INSTRUMENT RANGE
IR2
C187
FEED FORWARD
FF2
C194
REVERSE SWITCH
RSW2
L154
OUTPUTS
CONTROL OUTPUT
CO2
C195
Description:
This subroutine computes a control output signal based on the above listed inputs
and parameters. The result is available as a database parameter CO. When the
control track command is zero,the module output will track the reset feedback by
back calculating the integrator term. When CTC is 1, the reset feedback is used by
the integrator to calculate the next output and should reflect the value (scaled
0-100%) of the value of the final control element. For standard PID controller
operation, reset feedback should equal OUT and control track command should
equal AUT.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-33