G02

SETPOINT GENERATOR - 2

NAME SYMBOL

DATAPOINT

INPUTS

REMOTE SETPOINT

RSP2

C192

REMOTE SP ENABLE

RE2

L163

SETPOINT TRACK INPUT

STV2

C200

SETPOINT TRACK SWITCH

SWSPT2

L164

PARAMETERS

SETPOINT TRACK ENABLE

STE2

L166

REMOTE GAIN

K12

C185

REMOTE BIAS

B12

C184

INSTRUMENT RANGE

IR2

C187

SETPOINT HI LIMIT

SH2

C197

SETPOINT LOW LIMIT

SL2

C198

OUTPUTS

SETPOINT SP2

L173

SETPOINT TRACK STATUS

SPTS2

L152

REMOTE STATUS

RMT2

L156

Description:
This subroutine selects one of three signals to load into SP. The signal selected is
either the Setpoint Track Value (STV), the Remote Setpoint (RSP) after being
multiplied by K1 and biased by B1 or the Setpoint Pushbutton Value. If the Setpoint
Track Switch (SWSPT) is zero (0) then SP = STV when Setpoint Tracking is enabled
(STE=1). When the previous condition is not in effect SP will equal (RSP x K1) + B1
if Remote Enable = 1 and the R/L pushbutton has set the Remote Switch to 1. When
none of the previous conditions are in effect the signal comes directly from the
setpoint increase and decrease pushbuttons.