G02 setpoint generator - 2 – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 32

G02
SETPOINT GENERATOR - 2
NAME SYMBOL
DATAPOINT
INPUTS
REMOTE SETPOINT
RSP2
C192
REMOTE SP ENABLE
RE2
L163
SETPOINT TRACK INPUT
STV2
C200
SETPOINT TRACK SWITCH
SWSPT2
L164
PARAMETERS
SETPOINT TRACK ENABLE
STE2
L166
REMOTE GAIN
K12
C185
REMOTE BIAS
B12
C184
INSTRUMENT RANGE
IR2
C187
SETPOINT HI LIMIT
SH2
C197
SETPOINT LOW LIMIT
SL2
C198
OUTPUTS
SETPOINT SP2
L173
SETPOINT TRACK STATUS
SPTS2
L152
REMOTE STATUS
RMT2
L156
Description:
This subroutine selects one of three signals to load into SP. The signal selected is
either the Setpoint Track Value (STV), the Remote Setpoint (RSP) after being
multiplied by K1 and biased by B1 or the Setpoint Pushbutton Value. If the Setpoint
Track Switch (SWSPT) is zero (0) then SP = STV when Setpoint Tracking is enabled
(STE=1). When the previous condition is not in effect SP will equal (RSP x K1) + B1
if Remote Enable = 1 and the R/L pushbutton has set the Remote Switch to 1. When
none of the previous conditions are in effect the signal comes directly from the
setpoint increase and decrease pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
2-25