F-cim 63 auto/manual switch - 2, Will equal s – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller CUSTOMIZATION GUIDE User Manual
Page 71

F-CIM 63
AUTO/MANUAL SWITCH - 2
NOT REUSABLE
INPUTS
NAME
SYMBOL
DATAPOINT
S
n-1
CONTROL OUTPUT
CO2
C195
A
AUTO ENABLE
AE2
L162
B
OUTPUT TRACK VALVE
OTV2
C201
C
OUTPUT TRACK SWITCH
SWOTV2
L165
PARAMETERS
OUTPUT TRACK ENABLE
OTE2
L167
HARD MANUAL LIMIT
HML2
L170
OUTPUT HIGH LIMIT
OH2
C181
OUTPUT LOW LIMIT
OL2
C182
OUTPUT SLEW RATE
T32
C190
OUTPUTS
S
n
OUTPUT
OUT2
C174
OUTPUT TRACK STATUS
OVTS2
L153
AUTO STATUS
AUT2
L155
Description:
This module selects one of three signals to load into OUT and become its output
(S
n
). The signal selected is either the Output Tracking Value (B), the Auto Value
(S
n-1
) or the Manual Pushbutton Value. If the Output Tracking Switch (C) is less
than 1, then S
n
= B when Output Tracking is enabled (OTE = 1). When the pre-
vious condition is not in effect S
n
will equal S
n-1
if Auto Enable (A) is
≥ 1 and the
A/M pushbutton has set the Auto Switch to 1. When neither previous condition is
in effect the selected signal comes directly from the output increase and decrease
pushbuttons.
MODULAR CONTROLLER CUSTOMIZATION GUIDE
3-19